DIGITAL METER®NOVA PD560 SeriesInstruction ManualPD562 & PD568PRECISION DIGITAL CORPORATION89 October Hill Road z Holliston MA 01746 USATel (800)
2. Front Panel Buttons and LED IndicatorsKEY FunctionPressing SET/ENT key for at least 3 seconds switches between the operating display andthe paramet
3. Parameter MapPV.LOPV.HIDSP.HDSP.LUS1US2LOCKDI.SLU.PWDG.CTL: Optional feature* : Menu only applies if controller includesthe 2 alarm relay output o
4. Operation Flow ChartOperation DisplayPower OnGroup Displaynote 1: Initial display when the unit is turned on.note 2: Only displayed when User Scree
5. Parameter Setup5.1 Input Group (G.IN)Press SET/ENT key to select input group. Press press S or T key to cycle throughgroups as shown below. (Refe
This parameter sets the display temperature unit for ºC or ºF.Its default selection is ºC.Refer to Table 1 when changing the temperature unit for the
+10ºC+1ºC-2ºCThe original temperature is shown within the range of 0ºC (Range Low) and 100ºC (Range High).Bias points have been used to adjust the dis
?NOTEDisplay ParameterSetting RangeUnit Default RemarkIN.SLIN.FLBSLRSLBSP1BSP2BSP3BS0BS1BS2BS3BS4Min InputValue Scale0.0 mV, VPV FilterOFF, 1 to 120se
5.2 Control Group (G.CTL)Press SET/ENT key to select control group. (Refer to parameter map in section 3.)PVTurning ON this parameter locks all setti
This parameter sets the high limit of the sensor input in the PV display. The PV value willnot display higher than this limit, however the control fu
5.3 Alarm Group (G.ALM)Press SET/ENT key to select alarm group. (Refer to parameter map in section 3.)The parameter to establish the type of alarm to
DisclaimerThe information contained in this document is subject to change without notice.Precision Digital Corporation makes no representations or war
SALMSALMW ONONXPV HighLimit AlarmPVW OFFPVOFFXPV LowLimit AlarmDBDBFig 3: Alarm OperationOperationNo. Alarm TypeStandby12345678Absolute Value High Lim
Display ParameterSetting RangeUnit Default RemarkALT3AL-3A3DBAlarm Type 3 Refer to Table 3: Alarm Selection ABS AH.FSet Value ofAlarm 3AEU (-100.0 to
5.4 Retransmission Group (G.RET)Press SET/ENT key to select retransmission group. (Refer to parameter map.)This parameter sets the type of retransmis
5.5 Communication Group (G.COM)Press SET/ENT key to select communication group. (Refer to parameter map.)The parameter to select the type of communic
Display ParameterSetting RangeUnit Default RemarkRP.TM Response Time0 to 10 (number of 10ms intervals)ABS 0 OptionCOM.PBAUDPRTYSBITDLENADDRCommunicati
6. Error Display and CorrectionError Message Action NeededE.SYS Needs RepairE.RJC Needs RepairSP DecimalFlashingCheck Comm CableS.OPN Check SensorErro
7.1 Dimensions and Panel Cutouts7. InstallationPD568m(inch) - for reference onlyUnits: m(3.78) (0.45)(3.92)(3.78)(4.23)(3.61x3.61)(4.72)(4.72)(3.62)(3
PD562m(inch) - for reference onlym92120+0.645 0+0.6 070(3.62)(1.77)(4.72)(2.76)4896(3.78)(1.89)99.644.6X91.6(3.92)(0.45)(1.76X3.61)Units:1/8 (H) DIN
Do not excessively tighten the mounting bracket screws. Excessive tightening may lead tocontroller or panel damage.!CAUTION7.2 Panel MountingPD568PD5
Always turn off the source circuit breaker and check to ensure the power is off to the controller through theuse of a tester prior to working on the w
1. Safety Guide and Specifications 52. Front Panel Buttons and LED Indicators 105. Parameter Setup115.1 Input Group (G.IN)135.2 Control Group (G.CTL)1
7.5 Terminal Assignment, Connections, and RatingsPD568--Rating: 250 VAC @ 3 A30 VDC @ 3 ARating: 250 VAC @ 1 A30 VDC @ 1 ARating: 250 VAC @ 1 A30 VDC
--20 19 18 17 16 15 14 13 12 1110987654321PD562Rating: 250 VAC @ 3 A30 VDC @ 3 ARating: 250 VAC @ 1 A30 VDC @ 1 AMax: 19200 bps100 - 240 VAC 50/60 HzO
Be sure to connect L (Hot), N (neutral), and GND (ground) as indicated.Failure to wire the power and ground as indicated could result in damageto the
To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breakerbefore wiring.7.8 Retransmission Output Conn
To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit breakerbefore wiring.7.10 Digital Input Connection
External ACPower(2) AC External RelayCR Filter (snubber)(Connect directly to the relay coil terminals)MeterR!CAUTION!CAUTIONRelay(Verify relay coil ra
NO.PROCESS FUNCTION SET POINT SIGNAL ALARM PID IN/OUT0 100 200 300 400 500 6000NPV ALT1 IN-T1ALT2 INT-U2ALT3 IN.RH3IN.RL4IN.DP5AL-1 IN.SH6AL-2 IN.SL7A
NO.PROCESS FUNCTION SET POINT SIGNAL ALARM PID IN/OUT0 100 200 300 400 500 60044454647484950RET51RETH52U RETL53s54e55r5657A58r59e60a616263646566676869
NO.PROCESS FUNCTION SET POINT SIGNAL ALARM PID IN/OUT0 100 200 300 400 500 600888990919293949596979899Read Only Location?NOTE PD560
NotesWarranty and Return InformationPrecision Digital warrants this product to be free from material defects and workmanship under normal use andservi
7.7 Signal Input Connection7.8 Retransmission Output Connection (RET)337.9 Relay Output Connection (RELAY)337.11 Use of an External Relay347.12 Commun
For Technical SupportCall: (800) 610-5239 or (508) 655-7300Fax: (508) 655-8990Email: [email protected] Sales Support or to place an order pleaseCa
1. Safety Guide and SpecificationsPrecautions Regarding This Instruction Manual(1) This manual must be kept in the possession of the end user and in a
!CAUTIONController Mounting Precautions Keep the input circuit wiring as far as possible away from power and ground circuits. Keep the units in 10
1.1 SPECIFICATIONSGeneralDISPLAY Dual 4 digits, red LED, -1999 to 9999DIN Sizes PV Display SP Display Weightmm (inch) mm (inch) g (oz)1/8 19.8 (0.78)
K1 -200 to 1370 -300 to 2500K2 -199.9 to 999.9 0 to 2300 > 0°C : ±0.1% FS ±1 digitJ -199.9 to 999.9 -300 to 2300 < 0°C : ±0.2% FS ±1 digitT -199
Relay OutputsRATINGS Alarm1: 250 VAC @ 3 A or 30 VDC @ 3 A (resisitive load)Alarm2, 3: 250 VAC @ 1 A or 30 VDC @ 1 A (resistive load)ELECTRICAL NOISE